Rainwater Harvesting Tank Sizing
Ref: MSMA 2nd Edition (2012), Chapter 6 — Rainwater Harvesting; Eq. 6.1, Tables 6.2–6.4
MSMA Equation 6.1 sizes the RWH tank as St = 0.01 × Ar (m³ per m² of roof) — equivalent to 10 mm of rainfall storage per unit roof area. This is a near-optimum value with ± 25 % variation (§6.4.5). Annual yield (AARY) values are scaled from Table 6.4 (base case: 1 m³ tank + 100 m² roof). For more accurate sizing, use the daily water balance model described in §6.4.3.
St = 0.01 × Ar (tank size m³ per roof area m²)
Ref: MSMA 2nd Edition (2012), Chapter 6 — Rainwater Harvesting; Eq. 6.1, Tables 6.2–6.4
Plan (horizontal projected) area of the roof
Nearest Town (Table 6.2 / 6.4)
e.g. toilet flushing 120 L/day, car wash 200 L/wash — see MSMA Table 6.1
Recommended Tank Size (St)
—m³
Engineering aid only — final design must be endorsed by a registered PE under BEM.